POWER FACTOR IMPROVED BY VARIABLE SPEED AC DRIVES
Mauri Peltola, ABB Oy, Drives
Would your mill benefit from power factor improvement?
Variable speed drives help solve the power factor problem—while
improving process control, saving electrical energy, and reducing machinery
wear.
AC induction motors are essential for industry and utilities.
Yet, as compared to other types of loads, the induction motor has a relatively
poor power factor, causing higher line currents, which cause additional
heat in line cables and transformers. The power factor is especially low
in cases when the motor is oversized for the application and, therefore,
running lightly loaded.
The use of variable speed AC drives (VSD) to control
motor speed can improve the power factor, thus reducing losses in the
supply cables and transformers. VSDs can also help managers avoid the
cost of investment in power-factor-correction equipment.
This article explains the reason for the phenomena,
which may result in the input current to the variable speed AC drive can
be lower than the output current. The article also gives some guidelines
when compared with fixed speed applications or other speed control methods
like DC drives.
What is the Difference Between Power Factor and
Cos f
Power Factor (PF) is an important measure for electrical systems. It is
defined as ratio of Real or Active Power, in total kilowatts, to total
Apparent Power, in kilovolt amps.
The Power Factor topic is of interest to a large number
of people. There sometimes seems to be confusion between the terms Power
Factor and cosf (phi). Just remember that the cosf is equal to Power
Factor only in cases where both system voltage (U) and system current
(I) are sinusoidal (in other words, cosf is equal to Power Factor only
when the voltage and current considered are at the same frequency). In
real-world electrical installations, both voltages and currents contain
harmonics, so in most cases, the Power Factor is not equal to cosf.
To understand Power Factor, it can help to consider
phasor diagrams. Figure 1 shows an electrical circuit.
The supply voltage U connected to the circuit is at a single frequency;
that voltage causes current I to flow through the components. According
to Ohms law, the voltage drop in each component is calculated by multiplying
the current I (in Amps) by the resistance (in Ohms). The phasor diagrams
for this circuit are shown in Fig. 2.

Figure 1. The three basic linear electrical components are in
serial connection with the voltage U, causing the current I to flow through
the circuit. The components are:
- Resistor R with resistance measured in Ohms and a voltage
drop uR
- Inductor with inductive impedance XL measured in Ohms and
a voltage drop uL
- Capacitor with capacitive impedance XC measured in Ohms and
a voltage drop uC
The voltages and currents in Fig. 1 can be illustrated
in phasor form in Fig. 2. The current I is common for each component in
the system, but the voltages are of different magnitude and their phasors
are in different directions—90 degrees apart from each other’s.
The three diagrams in Fig. 2 show the steps for defining the voltage phasors
and the angle between the total voltage U and the current I. As result,
we get the definition for the cosf:
Figure 2. The current phasor I rotates in phase
with the voltage vector uR, but it is lagging the voltage phasor uL and
leading the voltage phasor uC. All phasors rotate counter-clockwise. Because
the uL and uC are pointing in opposite directions, they are subtracted
and the difference uX is the reactive component of the total system voltage.
The uR is the active or real component and the phasor sum of these voltages
is the total voltage U. The cosine of the angle j between total voltage
U and the active voltage uR is the Power Factor of an ideal system, which
is known as cosf. If U and uR have one single, fundamental frequency,
cosf is sometimes called displacement Power Factor.
To further explain, power factor is sometimes visualized
with a horse pulling a railroad car down a railroad track. Because the
railroad ties are uneven, the horse must pull the car from the side of
the track. The horse is pulling the railroad car at an angle to the direction
of car’s travel. The power required to move the car down the track
is the real power. The effort of the horse is the total (apparent) power.
The car will not move sideways. Therefore the sideways pull of the horse
is wasted effort or reactive power. These three different power vectors
are shown in Fig. 3.
Figure 3. The Power factor definition by using power vectors.
In summary:
- Power Factor (PF) is the Real Power divided by Apparent Power
- Power Factor of the system with sinusoidal current and voltage
is cos j
- In both cases, the value of PF is from 0 to 1, sometimes given
as 0 to 100%
- The real-world PF is influenced by harmonic disturbances and
other non-linearities
- The real-world PF is therefore lower than with sinusoidal current
and voltage
When should the power factor be improved?
Power plant generators usually are designed for PF = 0.8 to 0.9. Therefore,
if the actual demand-side power factor is lower than 0.8, either the generator
current increases above the rated current or the active power output has
to be limited. For that reason, the power companies put limits on reactive
power consumed by the customers. The limits usually are set for large
industrial or public customers only.
Customers have to pay a power factor penalty if power
factor falls below a certain limit. The limits can vary widely from 0.8
to 0.97. The presence of electric motors connected to the power line is
the main reason for reduced power factor. The rated power factor of a
standard motor depends on its rated power and, typically, is around 0.85
but can be much lower if the motor is lightly loaded. This topic will
be studied in the next section.
Why do electric motors cause low power factor?
The use of AC induction motors is essential for industry and utilities.
AC induction motors consume more than 50 per cent of the energy used in
industry. As compared to other type of loads, motor loads have relatively
poor power factor. Poor power factor causes higher line currents, which
causes additional heat in line cables and transformers. The power factor
is especially low in cases when the motors are oversized and are running
with a light load.
Figure 4. Line current and power factor of a
55 kW AC induction motor as function of the motor load.
To produce the required rotating torque and speed, the
induction motor takes both active current and reactive current from the
power supply. The rotating torque of the motor is created as an interaction
between the active current component and the magnetic field. The field
is produced by the reactive current component. Light load takes less active
current but the magnetic field, as well as the reactive current, stays
constant. This means that the power factor decreases with decreasing load,
as shown in Fig. 4. At the full load, the current is
mainly active but, at the light load, the current is mainly reactive.
How can the power factor be improved?
There are many different methods to improve the power factor or compensate
for the reactive power.
At the power plant, the excessive reactive power can
be compensated by increasing the excitation of synchronous generators,
or by using separate rotating synchronous compensators. At transmission
or transformer stations, the reactive power can be compensated by power-factor-correction
capacitors. The capacitors can be installed to improve the power factor
for a single load or an entire power system.
At the plant level, the power factor correction can be
accomplished by using power-factor-correction capacitors, or by using
variable speed AC drives. When AC drives are used, power-factor-correction
capacitors should not be used, because it is usually unnecessary, and
because drive harmonics could damage power factor capacitors.
The principle of variable speed AC drives
On a pulse width modulated (PWM) drive with a diode bridge converter input,
the power factor to the AC line is near unity (see Fig. 5).
The output may have an inductive (lagging) power factor, due to the motor’s
inductive reactance. However, the motor’s reactive current is circulated
between the motor and the inverter bus capacitors—not to the input
line.
Figure 5. A variable speed AC drive input consists
of a rectifier bridge that converts the line AC voltage to DC voltage.
The smoothing of the DC voltage is made via an inductor (L) and capacitor
(C). The DC voltage (Ud) then is converted in the inverter to variable
frequency and variable voltage AC that is connected to the AC motor. The
switches V1 to V6 in the inverter are very fast semiconductors, usually
insulated gate bipolar transistors (IGBT) in modern drives.
Because of the fast switching inside the AC drive, there
is a risk of electromagnetic emissions. Emissions can be both conductive
and radiating interference. International regulations set limits on both
low- and high-frequency emissions. With the use of filters, screening
and suitable mechanical construction inside the drive cabinet, it is possible
to meet the electromagnetic compatibility (EMC) standards.
How variable speed AC drives improve power factor
Let’s study the currents of the above mentioned 55 kW/400V motor
and drive system:
Motor: motor mechanical power = 55 kW,
Input U = 400 V, efficiency = 94.4% and power factor = 0.89
Motor electrical input power= 55 kW/0.944 = 58.3 kW
Motor electrical KVA = kW/PF = 65.5
AC drive: Output P = 58.3 kW, 94.5 A
Input
U = 400 V, efficiency = 98% and power factor = 0.96
Drive input power = 58.3 kW/0.98 = 59.5 kW
Drive input KVA = 62.0
One can see that the drive input current from the supply
is 5 amps, or more than five percent (94.5 versus 89.5 amps), lower than
the drive output current to the motor. The active power input, instead,
is 1.2 kW (58.3 versus 59.5 kW) higher than the output from the drive.
The difference in drive input and output power factor
is how the variable speed AC drive can improve the power factor and how
the drive output current can be greater than the input current. This can
help reduce losses and save money for the mill.
The power losses in the power line, transformers and
cables are proportional to the square of the current. We can estimate
the following:
- Assume the average load on the 55 kW motor is 35 kW.
- From Fig. 4, the motor current at 35 KW is 65 amps; the AC drive
input current under these conditions is 60 amps.
- The AC drive reduces the input current from 65 A to 60 A.
- The reduction of losses when operating the motor from an AC drive
is then:
If total losses on the supply side are 5% of the average load, the AC
drive can reduce the losses to about 4%. The reduction on the total power
consumption, as well as reduction on money spent, is 1 %.
Note that the original reason to install an AC drive
is not the power factor improvement but better process controls, energy
savings in the process, and/or reduced wear of the machinery. Power factor
improvement is a positive side effect.
Power factor comparison between AC and DC drives
The main difference between standard AC and DC drives is that PWM AC drives
have a diode rectifier on the front end while DC drives have an SCR rectifier.
The control principle of the SCR rectifier is based on phase control with
line commutation, causing a phase shift between voltage and current. The
lower the speed, the larger the phase shifts. This reduces the power factor
of DC drives, especially in the lower speed ranges (as shown in Fig.
6).
Figure 6. Power factor of AC and DC drives as
function of motor speed.
Conclusions
The power factor topic is interesting and important for a number of parties
within the power generation and consumption marketplace. Industrial, commercial
and domestic customers want to get the most cost-effective electrical
installation to serve their machinery. Low power factor can mean extra
losses and penalty payments to the utility for excessive reactive power.
On the other hand, power production and transmission companies want to
sell as much active power as possible to their customers. Low power factor
can reduce the generating and transmission capacity.
Manufacturers of power-factor-correction equipment are
willing to sell capacitor banks and automation equipment to help improve
the power factor. Consultants also have an interest to help the power
companies, consumers and other interest groups with audits and plans for
better energy economy and achieving higher power factors. Finally, drives
and motors manufacturers can also help to improve the power factor with
variable speed drives. VSDs help solve the power factor problem—while
improving process control, saving electrical energy, and reducing machinery
wear.
Mauri Peltola is past director of marketing for ABB
Oy, Finland., ABB Oy, Drives. or more information on ABB Drives and Motors,
Contact: Ken Graber, ABB Inc., Automation Technologies, Drives and Motors,
16250 West Glendale Drive New Berlin, WI 53151-2840, Tel: (262) 780-3873,
Fax: (262) 785-8501; e-mail: ken.j.graber@us.abb.com
|